City of Morgan Hill

Sanitary Sewer Flow Monitoring and Inflow/Infiltration Study

12-0248 AEG CofMorganHill FM Rpt.docx

Page 4 of 46

Basin Inflow and Infiltration Analysis Results

Due to potential cross-connections between basins, the I/I results for Basins 7 and 8 are shown

together, labelled “Basin 7/8”. The individual results for Basin 7 and 8 are presented as sub-headers

and for informational purposes only to be used at the reader’s discretion.

Table 2 s

ummarizes the flow monitoring and I/I results for the nine flow monitoring basins that were

isolated during this study. Infiltration and inflow rankings are shown such that 1 represents the highest

infiltration or inflow contribution and 9 represents the least. Basins that ranked 1, 2 or 3 in a category

are color coded red. Please refer to the

I/I Methods

section for more information on inflow and

infiltration analysis methods and ranking methods.

Table 2. I/I Analysis Summary

Metering

Basin

ADWF

(mgd)

Peak I/I

Rate

(mgd)

Combined I/I

(gallons)

Inflow

Ranking

RDI

Ranking

Evidence

of High

GWI?

Combined

I/I

Ranking

Basin 1

0.19

0.23

56,400

7

4

No

7

Basin 2

0.17

0.13

47,200

9

T7

No

8

Basin 3

0.18

0.46

166,200

1

3

No

1

Basin 4

0.21

0.41

114,100

2

5

No

4

Basin 5

0.27

0.18

90,900

6

2

No

5

Basin 6

0.35

0.57

136,300

5

T7

Yes

6

Basin 7/8

0.40

0.67

230,300

3

T7

No

2

Basin 7

0.24

0.57

177,700

No

Basin 8

0.16

0.21

52,000

No

Basin 9

0.13

0.34

133,300

4

1

No

3

Basin 10

0.12

0.11

16,400

8

6

No

9

System

2.65

2.97

1,135,500

The following inflow/infiltration analysis results are noted:

Inflow:

Basins 3, 4, 7/8 and 9 ranked highest for normalized inflow contribution.

♦ If isolated, Basin 7 ranks highly within the Basin 7/8 basin and highly within the collection

system.

Rainfall-Dependent Infiltration:

Basins 3, 5 and 9 ranked highest for normalized RDI

contribution.

Groundwater Infiltration:

Basin 6 had GWI rates that were

above

the WEF typical low-to-

average ratio, indicating excessive groundwater infiltration.

Combined I/I:

Basins 3, 7/8, 9 and 4 ranked highest for normalized combined I/I contribution.

♦ If isolated, Basin 7 ranks highly within the Basin 7/8 basin and highly within the collection

system.