Simon Storage, Fluorobenzene Gantry / Tank 24

Instrument & Electrical Installation Tender Package

DOCUMENT REF: SI347001.INS

ISSUE: B DATE: 13.10.97

PAGE: 15 OF 23

3.3

Scope

The purpose of this project is a Fluorobenzene loading/offloading gantry and transfers

to/from Tank 24.

An overview drawing SI347001 details the cable and installation requirements.

All junction boxes, instruments, stop/starts and MCC will be provided free issue.

It is the Contractors responsibility to provide all rack, tray, cable, glands, fixings and

markers.

3.3.1

Rack and Tray

A new 300mm heavy duty tray is to be provided for instrumentation signals. This tray will

run above the existing electrical tray from the point where the underground cables rise at

the rear of the bund wall on enclosure B to the new gantry.

A new 300mm heavy duty tray is to be provided from the existing electrical tray adjacent to

the pipebridge on enclosure B bund wall, across the pipebridge to the new gantry.

Local trays are to be installed around the gantry for both instrumentation and electrics.

3.3.2

Mounting of Equipment

The Contractor is to take delivery of and install the following free issue equipment:-

Gantry Area

Scully EEx’d’ Enclosure.

Scully EEi Indicator, Plug and Socket Assembly.

Horn.

Gantry Control Unit JB.

Gantry Pneumatic Panel.

D.P. Transmitter.

Batcher.

I.S. Junction Box.

Offloading Pump Stop/Start Station.

Road Loading Pump Area

EEx’e’ Junction Box.

Road Loading Pump Stop/Start Station.