Simon Storage, Fluorobenzene Gantry / Tank 24
Instrument & Electrical Installation Tender Package
DOCUMENT REF: SI347001.INS
ISSUE: B DATE: 13.10.97
PAGE: 15 OF 23
3.3
Scope
The purpose of this project is a Fluorobenzene loading/offloading gantry and transfers
to/from Tank 24.
An overview drawing SI347001 details the cable and installation requirements.
All junction boxes, instruments, stop/starts and MCC will be provided free issue.
It is the Contractors responsibility to provide all rack, tray, cable, glands, fixings and
markers.
3.3.1
Rack and Tray
A new 300mm heavy duty tray is to be provided for instrumentation signals. This tray will
run above the existing electrical tray from the point where the underground cables rise at
the rear of the bund wall on enclosure B to the new gantry.
A new 300mm heavy duty tray is to be provided from the existing electrical tray adjacent to
the pipebridge on enclosure B bund wall, across the pipebridge to the new gantry.
Local trays are to be installed around the gantry for both instrumentation and electrics.
3.3.2
Mounting of Equipment
The Contractor is to take delivery of and install the following free issue equipment:-
Gantry Area
Scully EEx’d’ Enclosure.
Scully EEi Indicator, Plug and Socket Assembly.
Horn.
Gantry Control Unit JB.
Gantry Pneumatic Panel.
D.P. Transmitter.
Batcher.
I.S. Junction Box.
Offloading Pump Stop/Start Station.
Road Loading Pump Area
EEx’e’ Junction Box.
Road Loading Pump Stop/Start Station.