BRAMHALL TERMINAL – BRM-SIS1 ANNUNCIATOR RELAY REPLACEMENT

PHILLIPS 66

16089RPT205B

PAGE 9

4.2 Proposed Modification

Description

Replace annunciator alarm repeat relays with units from a

different supplier

Proposed

Safety Integrity Level

Not Applicable, Status signal only

Reason for the

Modification

T

he terminal has been experiencing failures of the annunciator

repeat relay during Nivotester pushbutton simulation testing. The

Nivotester simulation test cycles the relay twice before returning

healthy, several units have failed to return healthy leaving a high high

high level alarm active. The relay is not part of the safety instrumented

system, safety integrity level (SIL) calculations and does not affect

the safety instrument function (SIF) of high high high level closing V1

ESD valve.

Hazards which may be

affected by the

modification

None

Impact on functional

safety as a result of the

proposed modification

None, units not SIL rated