Note:

If the expansion valve tests did not cause the

low pressure gauge needle to rise and drop,

and if the other procedures described did not

correct the problem, the expansion valve is

defective. You must recover all refrigerant

from the system again, and replace the expan-

sion valve and receiver-drier. Evacuate and

recharge the system with refrigerant, then

check AC operation and performance.

0

100

200 300

400

500

HIGH

TEMPERATURE

LOW

TEMPERATURE

150

120

90

60

30

0

10

20

30

Expansion Valve (TXV) Stuck Open

LOW SIDE HIGH

HIGH SIDE NORMAL

Tip:

Air from vents in the cab is warm or only slightly

cool.

Cause:

The expansion valve is stuck open and/or the capil-

lary tube (bulb) is not making proper contact with

the evaporator outlet tube. Liquid refrigerant may

be flooding the evaporator making it impossible for

the refrigerant to vaporize and absorb heat nor-

mally. In vehicles where the TXV and sensing bulb

are accessible, check the capillary tube for proper

mounting and contact with the evaporator outlet

tube. Then perform the following test. If the TXV is

not accessible, then proceed to

Repair Procedure.

Test:

1.

Operate the AC system on it’s coldest setting for

a few minutes. Carefully spray a little nitrogen

or other cold substance, on to the capillary tube

coil (bulb) or head of the valve.

2.

The low pressure (suction) side gauge needle

should now drop on the gauge. This indicates the

valve has closed and is not stuck open. Repeat

the test, but first warm the valve diaphragm

with your hand.

Manifold Gauge Set Readings

Figure 8-10

Gauge reading, expansion

valve (TXV) stuck open.