Chapter 8
– Troubleshooting & Service Procedures
8-16
Go to Chapter Start-
Table of Contents-
Index3.
If the low side gauge shows a drop again, the
valve is not stuck. Clean the surfaces of the
evaporator outlet and the capillary coil or bulb.
Make sure the coil or bulb is securely fastened to
the evaporator outlet and covered with insula-
tion material. Operate the system and check per-
formance.
Repair Procedure:
If the test did not result in proper operation of
the expansion valve, the valve is defective and
must be replaced. Recover all refrigerant from
the system and replace the expansion valve and
the receiver-drier. Evacuate and recharge the
system with refrigerant, then check AC opera-
tion and performance.
0
100
200 300
400
500
HIGH
TEMPERATURE
LOW
TEMPERATURE
150
120
90
60
30
0
10
20
30
System High Pressure Side Restriction
LOW SIDE LOW
HIGH SIDE NORMAL-TO-HIGH
Tip:
Air from vents in the cab is only slightly cool.
Look for sweat or frost on high side hoses and
tubing, and frost appearing right after the point
of restriction. The hose or line may be cool to the
touch near the restriction.
Cause:
There could be a kink in a line, or other restric-
tion in the high side of the system.
Figure 8-11
Gauge reading, system high
pressure side restriction.