A small project design was changed on site.

Site change used a decommissioned module.

The modification was tested and worked.

ESD functionality was not tested as not part of the small

project modifications.

The decommissioned module had a connection to ESD rail,

which was not identified on drawings or during wiring

changes.

Result was that the change prevented the ESD system

from functioning.

Project 2: Findings