Local Fuel – Shoreham Oil Terminal
Gasoline Ship Import – Layers of Protection Analysis
P & I Design Ltd
DOCUMENT NO: LF364002_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: E DATE: 30.07.15
Tel: + 44 (0)1642 617444
PAGE 22 OF 38
Fax: + 44 (0)1642 616447
www.pidesign.co.uk5.3.2
Initiating Event Likelihood (Ref. PSLG Guidelines, Appendix 2, Clauses 55-57)
Initiating events were determined using a demand tree. The meeting considered a number
of events that could lead to the scenario considered and the following events were detailed.
Overfill of tank
Three of the initiating events were identified as the controlling factors in a possible
overfill:
Incorrect Routing on import
Incorrect Ullage in receipt tank. (Not enough ullage to take full import quantity)
Failure of ATG (Sticks or reads low)
Initiating events 4 & 5 were not considered as credible and the frequency of the event in
I.E. 6 was considered so low as to be negligible.
Failure of ATG
whilst filling
(I.E. 3)
Incorrect
Routing on
import (I.E. 1)
Incorrect
Ullage in
receipt tank
(I.E. 2)
Valve failure
(or passing)
(I.E. 4)
Changes in
filling rate (I.E.
5)
Failure of ship
operator to terminate
import (I.E. 6)