Background Image
Table of Contents Table of Contents
Previous Page  56 / 64 Next Page
Information
Show Menu
Previous Page 56 / 64 Next Page
Page Background

54

Wire & Cable ASIA – May/June 2016

www.read-wca.com

Formulation

LOI, %

HB-1

24

VB-1

27

VB-2

27

Figure 5

:

Effect of conductor type on uncharred length for

different formulations

Table 2

:

Limiting Oxygen Index of the flame-retardant

formulations studied

Solid - 30 mil

Stranded - 30 mil

Solid - 60 mil

Stranded - 60 mil

Uncharred length (mm)

3.2 Effect of conductor type (Solid vs stranded)

Even though a systematic study of the effect of insulation

thickness on burn properties for low voltage wire is

not available in the literature, similar studies have been

conducted for other flame retardant articles, an example of

which is fabrics for upholstery or children’s clothing

[3]

.

Comparison of such studies with flame retardant wires

needs to be made with some caution since the presence

of a metallic conductor with its high thermal conductivity

provides a thermal sink for the hot insulation and adds

to the complexity in understanding the effects of various

construction and geometric parameters of the polymeric

layer.

In this study, another aspect of the conductor, ie, solid vs

stranded copper, is investigated for its effect on the burn

behaviour of the wire.

Figure 3

shows the effect of the conductor type on burn

duration for all the formulations in a VW-1 burn test for

30 mil insulation thickness. For both the vertical burn

rated compositions, the flame extinguishes much sooner

for the solid conductor than that for the stranded ones,

suggesting that using solid conductor provides a better

flame-retardance for the wires.

One possible reason for the superior performance of the

system with solid conductor may be due to the intimate

contact it provides with the insulation, thereby acting as a

better dissipator of heat from the polymer.

For the stranded conductors, on the other hand, the

voids between the polymeric layer and solid copper act

as thermal insulation and thus trap more heat inside the

polymer. The difference is significant since passing VW-1

burn test requires the burn duration to be less than 60

seconds for the samples. For both the vertical burn rated

formulations, when a stranded conductor is used, the

samples exceed the maximum limit for burn duration, thus

failing the test.

In fact, for the VB-2 sample, the entire length of the wire is

consumed, leaving no uncharred length (shown in

Figure 5

).

On the other hand, the constructions with solid conductors

pass the VW-1 test with comfortable margins.

The burn duration data shown in

Figure 3

for the HB-1

samples could also be somewhat misleading without

considering the fact that for both instances (solid and

stranded), the wires burn through the flag, leaving

no uncharred sample. Interestingly, even though the

VB-1 stranded sample burns for a long time (>60 sec),

it still leaves substantial uncharred length after flame

extinction.

The effect of solid vs stranded conductor for 60 mil

insulation thickness is illustrated in

Figure 4

. As seen for

30 mil thickness, both solid and stranded HB-1 samples

burn completely through their entire length. The same

is true for the VB-2 sample with stranded conductor.

The results again show that for identical formulation

and geometry, stranded conductors exhibit a poorer

burn performance.

For the same VW-1 burn tests conducted to compare the

effect of conductor type, the results are also expressed by

the uncharred length of the wire samples for the vertical

burn rated formulations in

Figure 5

.

As discussed earlier, irrespective of insulation thickness,

both the VB-2 stranded wires burned completely and did

not leave any uncharred length. Overall, the data again

shows the superior burn performance of wires made

with solid conductors as opposed to the stranded ones.

The results also confirm that the VB-1 formulation is

comparatively better in flame retardance than the VB-2

material.

In fact, for the 30-mil stranded wire, which is the most

difficult condition for a formulation to pass VW-1 test

among all the conditions studied, the VB-1 sample came

very close to passing with only the burn duration time

exceeding the maximum allowed time by a few seconds.

On the other hand, the VB-2 sample completely burned out

even for the 60 mil insulation thickness when a stranded

conductor was used.

As a side experiment, the Limiting Oxygen Index (LOI) for

the three FR formulations was measured and the results

are shown in

Table 2

.

The LOI data confirms that the VB-1 and 2 formulations

are superior to HB-1 composition in flame retardance.

However, the differences between the two vertical burn

rated materials cannot be distinguished by the LOI data

even though they showed marked difference in the VW-1

test.

4 Conclusions

Investigation into the effects of the two important cable

construction parameters, namely insulation thickness

and conductor type (solid vs stranded), for VW-1 burn

performance provides some important insights.

The effect of insulation thickness very much falls in line

with the behaviour seen for the other FR articles such as

textiles and home furnishings, where larger thickness

provides better flame resistance

[5]

.