Safety Instrument System Functional Safety Assessment Stage 5

P & I Design Ltd

DOCUMENT NO: LF364100_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 15.06.2015

Tel: + 44 (0)1642 617444

PAGE 19 OF 32

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

5.3 SIL Verification

Document LF364006_RPT Revision A was reviewed as part of this FSA. It was noted that it

has been written for inclusion of the new SIL rated XV162 actuator but not for the later

modification for the change of two gasoline tanks to Marine Oil tanks. Again, depending on

the outcome of Action 1, this document may also need revising, see also Action 7 regarding

the title.

As part of the FSA SIL Verification, the data used to calculate the pfd was reviewed and

detailed below:

Sensor:

The sensors employed within the SIS are Drexelbrook Intellipoint RF transmitters providing

a 4 – 20mA signal, although this is not analog in normal understanding of analog. The devices

utilises this as a carrier signal and depending on the status of the sensor provides a

corresponding mA signal: 8mA - Alarm, 16mA - Normal, 22mA – Fault.

The failure data is provided as:

The calculation within the SIL Verification document Section 6.5 utilises the above data and

confirms that a PFD = 3.38x10

-4

it is noted that the calculation refers to this pfd being for

perfect testing and imperfect testing provides a pfd of 8.57x10

-4

. The device has a SFF of 0.93

and as such satisfies HFT = 0 in accordance with BS EN 61508.

Action 8: