Safety Instrument System Functional Safety Assessment Stage 5

P & I Design Ltd

DOCUMENT NO: LF364100_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 15.06.2015

Tel: + 44 (0)1642 617444

PAGE 21 OF 32

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

Final Element:

The PILZ safety relay provides normally open volt free contacts. A 24V dc supply originating

in the Rotork actuator is fed through these contacts and back to the hardwired ESD circuit

contained with the actuator. The actuator is capable of being operated remotely, however,

without the 24V dc input to the ESD circuit the actually will fail closed.

It is certified to BS EN 61508 by SIRA for use in a SIL 2 SIS with HFT = 0. As it has fairly

recently being certified it also has a Systematic Capability assessment with a resulting SC3.

The value used for the actuator in LF364006_RPT utilises the average value from the certified

data. This FSA checked what the overall pfd of the SIS would be if the worst case value was

used, this changed the PFD

SYS

form 3.57x10

-3

to 3.94x10

-3

which is still within the required

5.00x10

-3

required from the LOPA.

The second part of the final element sub-system is a PEKOS ball valve. Exida have certified

this component as SIL 3 capable. In accordance with BS EN 61511 the device can be used in

a SIL 3 with HFT = 1 and SIL 2 with HFT = 0.

Calculation Summary:

From the supplied components and BS EN 61508 certification it confirms that the system does

comply to the requirements of a PFD and HFT for a SIL 2 SIS, with a PFD

SYS

of 3.57x10

-3

.