Local Fuel – Shoreham Oil Terminal
Gasoline Ship Import – Layers of Protection Analysis
P & I Design Ltd
DOCUMENT NO: LF364002_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: E DATE: 30.07.15
Tel: + 44 (0)1642 617444
PAGE 7 OF 38
Fax: + 44 (0)1642 616447
www.pidesign.co.ukScenario 2
- Overfill of gasoline tank during import from a ship leading to a potential
flash fire causing a single on-site fatality and no off-site fatalities.
Risk Tolerance Criteria
=
1.0 x 10
-6
/year
Frequency of Mitigated Consequence
=
3.30 x 10
-7
/year
The risk tolerance criteria is within the Broadly Acceptable region for up to 1 fatality
(Table 3 - Tolerable Risk Criteria). The frequency of Mitigated Consequence with a mid-
range SIL 2 SIS is well within the “Broadly Acceptable” region.
Scenario 3
- Overfill of gasoline tank during import from a ship leading to a potential open
vapour cloud explosion, bund wall damage and release of Products (Diesel, Kerosene,
Marine Gas Oil or Gas Oil), Gasoline, or fire-fighting water/foam causing a potential
MATTE which would constitute a threat to the environment (Consistent with Table 4 -
Environmental Tolerable Risk Frequency).
Risk Tolerance Criteria
=
1.0 x 10
-6
/year
Frequency of Mitigated Consequence
=
1.58 x 10
-7
/year
The risk tolerance criteria is within the Broadly Acceptable region for a severe
environmental consequence (Table 4 - Environmental Tolerable Risk Frequency). The
frequency of Mitigated Consequence with a mid-range SIL 2 SIS is within the “Broadly
Acceptable” region.
Scenario 4
- Overfill of gasoline tank during import from a ship leading to release of
Product (Diesel, Kerosene, Marine Gas Oil Gas Oil or Gasoline and a potential MATTE
which would constitute a threat to the environment (Consistent with Table 4 -
Environmental Tolerable Risk Frequency).
Risk Tolerance Criteria
=
1.0 x 10
-6
/year
Frequency of Mitigated Consequence
=
6.59 x 10
-8
/year
The risk tolerance criteria is within the Broadly Acceptable region for a severe
environmental consequence (Table 4 - Environmental Tolerable Risk Frequency). The
frequency of Mitigated Consequence with a mid-range SIL 2 SIS is within the “Broadly
Acceptable” region.
The above were achieved with a mid-range SIL2 protection layer which would close the
common gasoline pipeline fail-safe actuated valve on initiation of any tank’s high high
level switch.