due to its lower carbon content,

which enhanced diffusion of iron and

zinc. Besides carbon, other alloying

elements could have an influence on

diffusion and consequently temperature

resistance time.

Wrapping Tests

Figure 12

shows wrapping tests of

the 3.4mm Zn and Zn5Al coated 1083

core wires taken from the ACSR cable

segments after 185 days at 190°C.

These tests were done by wrapping

the wire around mandrels having

1, 2 and 3x the wire diameter.

At this and at all lower time durations,

no coating failures were seen in any of

the Zn or Bezinalized core wires.

For the 1.85mm 1005 wires, failures

were noticeable in the case of the Zn

coated wire, but not with the Zn5Al

coated wire (

Figure 13

).

The Zn coated 1.85mm 1005 wire

can be seen to become progressively

worse with time at 190°C as shown in

Figure 14

.

At higher temperatures, defects in

coatings on the 3.4mm wires from 1x

wrapping tests are noticeable, starting

at 225°C after 14 days as shown in

Figure 15

.

Similar defects were seen with 3x

wrapping conditions.

Under these conditions, small ruptures

begin to appear in the Zn coating. No

ruptures are seen in the Zn5Al coating,

but a ‘crosshatch-like’ texture begins

to appear on the Zn5Al coating which

is believed not to be due to coating

failure, but is believed to be due to

brittleness in an oxidized Zn-Al ‘skin’

developed on the coating during the

high temperatures.

Similar wrappings for 3.4mm 1083 after

28 days at 225°C show no significant

differences from those exposed for

14 days at the same temperature.

Figure 16

shows 1x wrappings for the

1.85mm Zn and Zn5Al coatings after

two and four weeks at 225°C. No

damage is seen for either coating after

two weeks, but the Zn coating clearly

Figure 12

:

1x, 2x and 3x wrapping tests for 3.4mm

1083 ACSR core wires after 185 days at 190°C

Figure 13

:

1x wrapping tests for 1.85mm 1005

wires after 185 days at 190°C

Figure 14

:

1x wrapping tests for 1.85mm

Zn-coated 1005 wire after 62 and 121 days at

185°C

62 days

2 weeks

4 weeks

121 days

Zn

Zn5Al

Zn

Zn5Al

Figure 15

:

1x wrapping tests for 225°C 3.4mm

1083 conditions, 2 magnifications

Figure 16

:

1x wrappings of 1.85mm trials at

225°C, two and four weeks, at two magnifications

2 weeks

2 weeks

4 weeks

4 weeks

Zn

Zn5Al

Zn

Zn5Al

Zn with Al

conductors

Zn without

Al conductors

Zn5Al with Al

conductors

Zn5Al without

Al conductors

Figure 17

:

1x wrappings of 3.4mm 1083 wires

after 245°C, 14 days with and without aluminium

conductors