Immingham Storage Company Limited – East Terminal

No.7 Switchroom - Basis of Design

P & I Design Ltd

DOCUMENT NO: SI451001_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 10.08.12

Tel: + 44 (0)1642 617444

PAGE 4 OF 12

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

3

ORIGINAL INSTALLATION

An 11kV supply from ABP feeds an 11000/3300/415V transformer located in an outside

location adjacent to the main office building. Information supplied indicates this to be

rated at 850kVA (500kVA at 3300V plus 350kVA at 440V). The 3300V supply from the

transformer feeds two fire pump starters located in No.3 Switchroom. The 415V supply

feeds all LV supplies in No.3 Switchroom, No.3 Pump House and No.7 Switchroom as

shown below.

11kV Supply From ABP

No.3 Switchroom

400A

Fused

Switch

(AC)

400A

Fused

Switch

(EE)

Various Loads

Various Loads

No.3 Pump House

Various Loads

Various Loads

(See section 5.2)

No.7 Switchroom

200A

P30025

P30015

Fire Pump

Starters

415V

(350kVA)

3300V

(500kVA)

It has not been possible to establish the maximum demand placed on the 415V supply from

the transformer. It is known however that the combined load of No.3 switchroom, No.3

Pump House and No.7 switchroom does not exceed 460A i.e. the transformer rating. Given

that there is a significant connected load in No.3 Switchroom it is also reasonable to

deduce that even though there are two separate 400A feeds to No.3 Pump House, these two

feeds combined do not exceed 400A in total.