Immingham Storage Company Limited – East Terminal

No.7 Switchroom - Basis of Design

P & I Design Ltd

DOCUMENT NO: SI451001_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 10.08.12

Tel: + 44 (0)1642 617444

PAGE 10 OF 12

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

5.3

Modifications not Reliant on ABP Decision

1.

Provide new MCC in No.7 Switchroom to replace Board fed from Switch EE i.e.

the board which is located in the compressor house end of the building. This will

enable this old board to be retired.

2.

Provide new MCC in No.7 Switchroom to replace Board fed from Switch AC. This

will enable this old board to be retired.

3.

Incorporate old No.7 Switchroom drives into new MCC and retire old No.7

switchroom

5.4

No.6 Switchroom

No.6 Switchroom is currently fed at 415V and limited to 200A capacity. This supply is

known to have a poor earth loop impedance value which impacts on electrical designs in

this switchroom. If a new 11kV supply becomes available from ABP (section 5.1) then

No.6 switchroom would be re-supplied from No.7 switchroom and the ABP 415V supply

retired. If a new supply is not available then the decision to re-supply No.6 from No.7

would be deferred until the new capacity and usage was fully understood.