Immingham Storage Company Limited – East Terminal

No.7 Switchroom - Basis of Design

P & I Design Ltd

DOCUMENT NO: SI451001_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: C DATE: 10.08.12

Tel: + 44 (0)1642 617444

PAGE 8 OF 12

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

5.1

New ABP 11kV Supply (No.7) – Retain ABP Supply to No.3 (3.3kV)

An option is to obtain a new 11kV supply to the terminal. This would be sited adjacent to

No.7 Switchroom and supply the LV board within. LV supplies would be distributed from

this point to No.3 and No.6 switchrooms, replacing LV supplies at those locations.

If this option became available the order of proposed works is as follows.

1.

Provide new 11000/400V transformer at No.7 Switchroom. LV board is capable of

accepting up to 2MVA transformer.

2.

Build a new LV switchroom adjacent to existing No.3 switchroom and supply this

from No.7 Switchroom LV Board

3.

Transfer loads from existing No.3 switchroom to new switchroom. On completion

the existing No.3 switchroom becomes a dedicated 3.3kV switchroom.

A single line diagram is shown below for this solution.

11kV Supply From ABP

11,000 /

415V

No.7 Switchroom

LV Switchboard

No.6 Switchroom

2MVA

3200A

MCC 1

MCC 2

630A 630A

Aquabio

630A 400A

LV

Board

(Ex

Switch

AC)

LV

Board

(Ex

Switch

EE)

400A 630A

No.3

Switchroom

630A

Spare

1250A

11kV Supply From ABP

No.3 Switchroom

Fire Pump

Starters

415V Tapping no

longer used

3300V

(500kVA)

Future Spares