Local Fuel PLC – The Shoreham Oil Terminal
Safety Instrument System Overfill Shutdown Conditions Proof Testing Procedure LFS-SIS1
P & I Design Ltd
DOCUMENT NO: LF364012_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: A DATE: 20.05.15
Tel: + 44 (0)1642 617444
PAGE 4 OF 22
Fax: + 44 (0)1642 616447
www.pidesign.co.uk3
SCOPE
Client / Company
-
Local Fuel PLC
Location / Facility
-
The Shoreham Oil Terminal
Plant Unit
-
Spirt Bund / Distillate Bund
Service
-
Storage Tank Overfill Protection
SIS Tag No
-
LFS-SIS1
SIF’s Tag No’s
-
SIF-1, SIF-2, SIF-3 & SIF-4
SIL
-
2
Lifecycle Stages
Stage 4
-
BS EN 61511 Clause 16 - SIS Operation and
Maintenance
Audience
This document has been produced for use by competent persons knowledgeable in testing
Safety Instrument Systems.
Brief System Description
SIF’s under test are to prevent the overfill of storage tanks when on import.
The system is classified as SIL2.
Full system description in LF364001_MNL Shoreham Oil Terminal LFS-SIS1
Procedure
This procedure outlines the necessary steps required to verify the correct equipment is
installed, the physical condition of the installed equipment and the functional operation
performs the SIF’s as designed.
Detailed in this report are the methods of test for each SIF.
The results of these tests will be recorded in this report, historical data will be recorded in
report reference LF364013_RPT - LFS-SIS1 Operation, Maintenance and Modification
Lifecycle and schedule reference LF364004_SCH - LFS-SIS1 Testing Lifecycle Matrix.
This report details shutdown condition testing whilst no transfer to the tanks is in operation.
All faults should be reported to the functional safety manager, with minor repairs carried out
if practicable. If further maintenance work is required the functional safety manager will
initiate it.