Local Fuel PLC – The Shoreham Oil Terminal

Safety Instrument System Overfill Shutdown Conditions Proof Testing Procedure LFS-SIS1

P & I Design Ltd

DOCUMENT NO: LF364012_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 20.05.15

Tel: + 44 (0)1642 617444

PAGE 4 OF 22

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

3

SCOPE

Client / Company

-

Local Fuel PLC

Location / Facility

-

The Shoreham Oil Terminal

Plant Unit

-

Spirt Bund / Distillate Bund

Service

-

Storage Tank Overfill Protection

SIS Tag No

-

LFS-SIS1

SIF’s Tag No’s

-

SIF-1, SIF-2, SIF-3 & SIF-4

SIL

-

2

Lifecycle Stages

Stage 4

-

BS EN 61511 Clause 16 - SIS Operation and

Maintenance

Audience

This document has been produced for use by competent persons knowledgeable in testing

Safety Instrument Systems.

Brief System Description

SIF’s under test are to prevent the overfill of storage tanks when on import.

The system is classified as SIL2.

Full system description in LF364001_MNL Shoreham Oil Terminal LFS-SIS1

Procedure

This procedure outlines the necessary steps required to verify the correct equipment is

installed, the physical condition of the installed equipment and the functional operation

performs the SIF’s as designed.

Detailed in this report are the methods of test for each SIF.

The results of these tests will be recorded in this report, historical data will be recorded in

report reference LF364013_RPT - LFS-SIS1 Operation, Maintenance and Modification

Lifecycle and schedule reference LF364004_SCH - LFS-SIS1 Testing Lifecycle Matrix.

This report details shutdown condition testing whilst no transfer to the tanks is in operation.

All faults should be reported to the functional safety manager, with minor repairs carried out

if practicable. If further maintenance work is required the functional safety manager will

initiate it.