Local Fuel PLC – The Shoreham Oil Terminal

Safety Instrument System Overfill Shutdown Conditions Proof Testing Procedure LFS-SIS1

P & I Design Ltd

DOCUMENT NO: LF364012_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 20.05.15

Tel: + 44 (0)1642 617444

PAGE 6 OF 22

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

5

PREPARATION

All Health and Safety / Permit To Work systems must be implemented before commencing

testing. LF364014_RPT – LFS-SIS1 RAMS is to be submitted for approval prior to the site

testing.

LFS-SIS1 is completely independent of the BPCS, no overrides or special preparations are

required to facilitate uncompromised testing.

Controlled copies of the following documentation will be required:-

LF364012_RPT - LFS-SIS1 Shutdown Conditions Proof Testing (this procedure)

LF364002_SCH - LFS-SIS1 Instrument Schedule

LF364003_SCH - LFS-SIS1 Testing Matrix

LF364011_RPT - LFS-SIS1 Documentation Verification to be completed prior to each

period of testing to confirm correct revisions of documentation.

A controlled copy of this procedure will be used to carry out the testing and will form part of

the lifecycle testing documentation.

Controlled copies of all documentation required for testing to be attached. In addition to

procedures documented in this report calibration certificates, engineers’ reports are to be

issued to each item as applicable.

The functional testing will be controlled and documented by a technician in radio contact

with testers in the switchroom and at field equipment locations as required.