Local Fuel PLC – The Shoreham Oil Terminal
Safety Instrument System Overfill Shutdown Conditions Proof Testing Procedure LFS-SIS1
P & I Design Ltd
DOCUMENT NO: LF364012_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: A DATE: 20.05.15
Tel: + 44 (0)1642 617444
PAGE 8 OF 22
Fax: + 44 (0)1642 616447
www.pidesign.co.uk6.5
Confirm no visible signs of additional
plant or parallel systems which could
affect the SIS or invalidate testing.
No new additional plant equipment or
BPCS systems.
Comment any issues in section 6.6.and
review / rectify prior to starting
functional testing.
6.6
Comments/Defects/ Remedial Actions
– Report ALL to System Keeper
Tested by
Position
Qualification
Sign
Date
System Keeper Acknowledgement
(Note: Signature confirms System keeper is advised of Comments/Defects/Remedial Actions and will initiate
terminal procedures for rectification works and/or isolation of plant as required)
Accepted by
Position
Qualification
Sign
Date