Immingham Storage Co Ltd – Immingham East Terminal - No4 Switchroom Tank Overfill Safety Instrument System
Logic Panel Factory Acceptance Test Procedure
P & I Design Ltd
DOCUMENT NO: SI483005_RPT
2 Reed Street, Thornaby, UK, TS17 7AF
ISSUE: A DATE: 05.03.13
Tel: + 44 (0)1642 617444
PAGE 7 OF 19
Fax: + 44 (0)1642 616447
www.pidesign.co.uk3.3
LOGIC PANEL WIRING INSPECTION
Equipment Required
Hand Tools, yellow highlighter, red pen.
Purpose of Test
To verify the logic panel internal wiring is satisfactory to proceed to powered functional testing. The logic
panel has been constructed and wired by a competent & reputable panel building company; initial quality
checks have been carried out prior to being available for witnessed factory testing.
Method Of Test
Result
3.3.1
A random sample of the following tests to be carried out. During the
procedure of functional testing the controlled copies of listed logic drawings will
be used to record, by highlighting (yellow), satisfactory compliance with actions
1 to 6. On completion of all functional testing, all logic drawings should be fully
highlighted. Errors and omissions will be corrected and noted in red.
1.
Terminals type and numbering conforms to logic drawings.
2.
Panel wire feruling conforms to logic drawings.
3.
Panel wire gauge and colour conforms to panel specification.
4.
Fuse and MCB ratings conform to logic drawings.
5.
Termination and crimps tight.
6.
Point to point wiring correct to logic drawings.
Actions/Comments
Sign
Date
Tested by