Table of Contents Table of Contents
Previous Page  66 / 189 Next Page
Information
Show Menu
Previous Page 66 / 189 Next Page
Page Background

Immingham Storage Co Ltd – Immingham East Terminal - No4 Switchroom Tank Overfill Safety Instrument System

Logic Panel Factory Acceptance Test Procedure

P & I Design Ltd

DOCUMENT NO: SI483005_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 05.03.13

Tel: + 44 (0)1642 617444

PAGE 11 OF 19

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

4.2.3 SYSTEM TRIP RESET

Equipment Required

Multi-meter, hand tools, links, yellow highlighter, red pen.

Purpose of Test

To verify the functionality of the system reset logic.

To verify the functionality of an fuse failure.

Method Of Test

4.2.3.1

Operate local reset pushbutton, confirming system trip reset relays

energised whilst reset depressed. Simulate a volt free input to remote reset

incoming terminals, incoming terminals linked reset relays energised, incoming

terminals open circuit reset relays de-energised.

4.2.3.2

Remove and replace fuse confirm relay de-energised whilst removed

and reset pushbutton activated.

Result

1.

Reset Relay R84.

2.

Reset Relay R85.

3.

Reset Relay R86.

Actions/Comments

Approvals (Note: Signature indicates acceptance of test with

actions/comments noted)

Sign

Date

Tested by