Local Fuel PLC – The Shoreham Oil Terminal

Safety Instrument System Overfill Shutdown Conditions Proof Testing Procedure LFS-SIS1

P & I Design Ltd

DOCUMENT NO: LF364012_RPT

2 Reed Street, Thornaby, UK, TS17 7AF

ISSUE: A DATE: 20.05.15

Tel: + 44 (0)1642 617444

PAGE 16 OF 22

Fax: + 44 (0)1642 616447

www.pidesign.co.uk

8

FAILURE MODE TESTING PROCEDURE

8.1

Failure Mode Functional Testing

Purpose of Test

To verify the correct FAILURE MODES of the System Description system.

To verify correct failure DIAGNOSTICS information.

Diagnostic information not displayed correctly could result in undetected tank overfill, system

unavailability or incorrect operational response.

Controlled Copy Documentation Required

LF364003_SCH - LFS-SIS1 Testing Matrix

Record results on LF364003_SCH Sheet 5 & 6.

Loop Sheets as listed on LF364001_REG - LFS-SIS1 Drawing Register

Step

Method of Test

Acceptance Criteria

Pass (

)

Fail (x)

Initial

8.1.1

Review procedure with operations and

testing personnel.

All personnel familiarised with the scope

of works and responsibilities

.

Comment any issues in section 8.1.6 and

review / rectify prior to starting testing.

8.1.2

Confirm plant preparations satisfactory

prior to each period of work and

following changes in plant conditions

or operations.

Record PTW No………………………….

Conditions satisfied as detailed on PTW

and RAMS.

Comment any issues in section 8.1.6 and

review / rectify prior to starting any site

work.

8.1.3

Confirm system healthy and reset by

comparing against information on

LF364003_SCH Sheet 1.

System reset as detailed on

LF364003_SCH Sheet 1.

Comment differences from SCH or if

found in tripped state in section 8.1.6.

8.1.4

Confirm all final element valves

tripped by the initiator under test are

open.

Correct FINAL ELEMENT valve

position and DIAGNOSTICS display at

control room SCADA as detailed on

LF364003_SCH Sheet 2.

Comment differences from SCH in

section 8.1.6.

8.1.5

Initiate and reset each FAILURE

MODE as detailed on LF364003_SCH

Sheets 5 & 6.

Highlight tests completed on controlled

copy of LF364003_SCH Sheets 5 & 6.

ACTION and DIAGNOSTICS as

detailed on LF364003_SCH Sheets 5 &

6.

System Reset as detailed on

LF364003_SCH Sheet 1.

Comment differences from SCH in

section 8.1.6

Failure Mode Functional Testing Continued on page 17